Rockwell Automation 1784-KTCS ControlNET Scanner Installation Instructions User Manual
Page 27
ControlNet Scanner Card
27
Publication 1784-5.35 – April 1999
Table B
ControlNet status interpretation
•
steady –
indicator is on continuously in the defined state.
•
alternating –
the two indicators alternate between the two defined states at the same time (applies to
both indicators viewed together). The two indicators are always in opposite states, out of phase.
•
flashing –
the indicator alternates between the two defined states (applies to each indicator viewed
independent of the other). If both indicators are flashing, they must flash together, in phase.
and
A
B
Cause:
Action:
off
no power
none or power up
steady red
faulted unit
cycle power or reset unit
If fault persists, contact your Rockwell
Automation representative or distributor.
alternating red/green
self-test
none
alternating red/off
incorrect node configuration
check network address and other
ControlNet configuration parameters
or
A
B
Cause:
Action:
off
channel disabled
program network for redundant media,
if required
steady green
normal operation
none
flashing green/off
temporary errors
none; unit will self-correct
la ing gr n o
node is not configured to go on line
make sure the configuration keeper node
is present and working ➀
flashing red/off
media fault
check media for broken cables, loose
connectors, missing terminators, etc.
no other nodes present on network
add other nodes to the network
flashing red/green
incorrect network configuration
cycle power or reset unit
If fault persists, contact your Rockwell
Automation representative or distributor.
➀ The configuration keeper node is the node responsible for distributing ControlNet configuration data to all nodes on the
network.
Important:
The LEDs do not apply to the network access port (NAP)
connection.