Rockwell Automation 1769-BOOLEAN Compact I/O BOOLEAN Module Installation Instructions User Manual
Page 24
![background image](/manuals/579834/24/background.png)
24
Publication 1769-IN077A-EN-P - May 2006
(3)
Sourcing Output - Source describes the current flow between the I/O module and the field device. Sourcing output circuits
supply source current to sinking field devices. Field devices connected to the negative side (dc common) of the field power
supply are sinking field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used
options.
Environmental Specifications
Specification
Value
Storage Temperature
-40…+85 °C (-40…+185°F)
Operating Temperature
0…60 °C (32…140 °F)
Operating Humidity
5…95% non-condensing
Operating Altitude
2000 m (6561 ft)
Vibration
Operating: 10…500 Hz, 5 g, 0.030 in. max peak-to-peak
Shock
Operating: 30 g panel mounted (20 g DIN-rail mounted)
Non-operating: 40 g panel mounted (30 g DIN-rail mounted)
Radiated and Conducted
Emissions
EN50081-2 Class A
Electrical /EMC
The module has passed testing at the following levels
ESD Immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3)
10V/m, 80…1000 MHz, 80% amplitude
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30…1000 MHz.
Certifications
Certification
Value
Agency Certification
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)