background image

6 FOUNDATION Fieldbus Junction Box

Rockwell Automation Publication 1788-IN006A-EN-P - September 2014

European Hazardous Location Approval

This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC and has been found to comply
with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has been
assured by compliance with EN 60079-15:2010 and
EN 60079-0:2012+A11:2013..

WARNING: This equipment shall be mounted in an ATEX-certified enclosure with a minimum ingress protection
rating of at least IP54 (as defined in IEC 60529) and used in an environment of not more than Pollution Degree 2
(as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a tool-removable
cover or door.

WARNING: Provision shall be made, either in the apparatus or external to the apparatus, to prevent the rated
voltage from being exceeded by transient disturbances of more than 140%.

WARNING: Secure any external connections that mate to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with this product.

WARNING: Do not disconnect equipment unless power has been removed or the area is known to be
nonhazardous.

WARNING: Do not disconnect equipment unless power has been removed or the area is known to be
nonhazardous.

WARNING: Secure any external connections that mate to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with this product

WARNING: This equipment shall be used within its specified ratings defined by Rockwell Automation.

WARNING: Devices shall be used in an environment of not more than Pollution Degree 2.