Rockwell Automation 1788-FBJB6 Foundation Fieldbus Junction Box Installation Instructions User Manual
Page 14
14 FOUNDATION Fieldbus Junction Box
Rockwell Automation Publication 1788-IN006A-EN-P - September 2014
IEC Temperature Code
T4
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 0.5g@10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 15g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Emissions
CISPR 11 (IEC 61000-6-4): Class A
ESD Immunity
IEC 61000-4-2:
6kV contact discharges, 8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…200 MHz
10V/m with 200 H 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4: ±3kV at 5 kHz on communication ports
Surge Transient Immunity
IEC 61000-4-5: ±2kV line-earth(CM) on communication port
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure Type Rating
None (open style)
Wire Size
Communications connections:
0.205... 0.823 mm
2
(24...18 AWG) solid or stranded copper wire rated
higer than 82 °C (179.6 °F), 1.2 mm (3/64 in.) insulation max.
Wiring Category
(1)
2 - on communication ports
Wiring Torque
(conductor in terminal)
0.5…0.6 Nm (4.4…5.3 lb-in)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
Specifications - FOUNDATION Fieldbus Junction Boxes
Specification
Value
1788-FBJB4R
1788-FBJB6