14 FOUNDATION Fieldbus Junction Box

Rockwell Automation Publication 1788-IN006A-EN-P - September 2014

IEC Temperature Code

T4

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 0.5g@10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 15g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g

Emissions

CISPR 11 (IEC 61000-6-4): Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges, 8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…200 MHz
10V/m with 200 H 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4: ±3kV at 5 kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5: ±2kV line-earth(CM) on communication port

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure Type Rating

None (open style)

Wire Size

Communications connections:
0.205... 0.823 mm

2

(24...18 AWG) solid or stranded copper wire rated

higer than 82 °C (179.6 °F), 1.2 mm (3/64 in.) insulation max.

Wiring Category

(1)

2 - on communication ports

Wiring Torque
(conductor in terminal)

0.5…0.6 Nm (4.4…5.3 lb-in)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.

Specifications - FOUNDATION Fieldbus Junction Boxes

Specification

Value

1788-FBJB4R

1788-FBJB6