Trunk Trip (1788-FBJB4R only)

If a trunk goes into over-current state, it will trip the specific trunk while keeping
the rest of the redundant bus active. The trip will remove the supply from the
over-current trunk and set the trunk LED to red. The fault latch does not
unlatch when the fault has been removed. You must reset the trunk trip by either
pressing the Reset button or setting DIP switches 3 and 4 to enable an auto-reset.

Specifications

Specifications - FOUNDATION Fieldbus Junction Boxes

Specification

Value

1788-FBJB4R

1788-FBJB6

Input Voltage

12…32V DC, 0.5 A, Class 2/SELV

Trunk Output Voltage

12…32V DC, 0.36 A,
resistive only

12…32V DC, 0.48A, Resistive
Only

Drop Output Voltage

12…32V DC, 40 mA, resistive only

Power Consumption

40 mA at 24V max

Drop Current

40 mA

Trunk Current

360 mA

480 mA

Trunk Trip Current

490 mA

N/A

Isolation Voltage

no isolation between communication channels

Temperature, Operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 ˚C (32…140 ˚F)

Temperature, Surrounding Air, Max

60 ˚C (140 ˚F)

Temperature, Nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
0…60 ˚C (32…140 ˚F)

North American Temperature Code

T4