Configure the 1769-ASCII Module as a Generic Module

6. Open the controller tags for monitor to enter the following configuration

parameters in the Local::C tag data members.

All other parameters are 0.

This is a controller-scoped configuration tag.

Data [ ] Word

Value (Decimal)

Meaning

0

0

Alternating mode

1

3

Framing is 8N1

2

0

9600 baud

3

80

Max Rx Characters

6

1

Use an Rx End delimiter, but exclude it from the input buffer

7

13

Use a Carriage Return as the Rx End delimiter

10

1

Produce data when available

12

80

Max Tx Characters