Configure the 1769-ASCII Module
Chapter 2
Stop Bits
Choose 1 or 2 (default) for the Stop Bits. Stop Bits appear dimmed Run mode. These are the Valid Data Bits, Parity, and Stop Bits combinations
Data Bits
Parity
Stop Bits
7
None
2
7
Even
1
7
Odd
1
7
Even
2
7
Odd
2
8
None
1
8
None
2
8
Even
1
8
Odd
1
Receive Data
Start Mode
• Ignore Delimiter (default)
• Exclude Delimiter
• Include Delimiter
Start Mode appears dimmed Run mode.
Start Delimiter
Valid values are any ASCII character (7 bit – 0…127; 8 bit – 0…255). These are the supported special characters.
Character
Description
$$
Dollar Sign ($24)
$’
Single Quote ($27)
$L
Line Feed ($0A)
$P
Form Feed ($0C)
$R
Carriage Return ($0D)
$T
Tab ($09)
Start Delimiter appears dimmed.
Termination Mode
Configure the channel’s termination mode. These are the valid values.
• Ignore Delimiter
• Exclude Delimiter
• Include Delimiter (default)
Termination Mode appears dimmed in Run mode.
Termination Delimiter
Configure the channel’s termination delimiter. Valid values are any ASCII character (7 bit – 0…127; 8 bit – 0…255). The following special
characters are supported.
Character
Description
$$
Dollar Sign ($24)
$’
Single Quote ($27)
$L
Line Feed ($0A)
$P
Form Feed ($0C)
$R
Carriage Return ($0D)
$T
Tab ($09)
Termination Delimiter appears dimmed in Run mode.
Transmit Data
Configure the channel’s termination mode. These are the valid values.
• Ignore Delimiter
• Exclude Delimiter
• Include Delimiter (default)
Termination Mode appears dimmed in Run mode.
Table 3 - Module Properties Dialog Box - Configuration Tab Parameter Descriptions (Continued)
Parameter
Description