Rockwell Automation 1753-L32BBBP-8A GuardPLC 1800 Controller User Manual
Page 22
22 GuardPLC 1800 Controllers
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Counters
Number of counters
2 (not electrically isolated)
Inputs
3 per counter (A, B, Z)
Input voltages
5V and 24V DC
High signal (5V DC): 4…6V
High signal (24V DC): 13…33V
Low signal (5V DC): 0…0.5V
Low signal (24V DC): -3…5V
Input currents
1.4 mA @ 5V DC
6.5 mA @ 24V DC
Input impedance
3.7 k
Ω
Counter resolution
24-bit
Input frequency, max
100 kHz
Triggered
on negative edge
Edge steepness
1 V/
μ
s
Pulse duty factor
1:1
Analog Inputs
Number of inputs
8 (unipolar, not electrically isolated)
External shunt
(for current measurement)
500
Ω
for 0…20 mA
Input values related to L-
Nominal Value: 0…10V DC or 0…20 mA with 500
Ω
shunt
Service Value: -0.1…11.5V DC or -0.4…23 mA with 500
Ω
shunt
Input impedance
1 M
Ω
Internal resistance of the
signal source
≤
500
Ω
Overvoltage protection
+15V, -4V
Resolution (A/D converter)
12-bit
Accuracy
0.1% @ 25 °C (77 °F)
0.5% @ 60 °C (140 °F)
Transmitter supplies
25.37…28.24V /
≤
46 mA, short-circuit proof
Safety accuracy
± 2%
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publicat
.
Technical Specifications – GuardPLC 1800 Controllers