Specifications – Rockwell Automation 1753-L32BBBP-8A GuardPLC 1800 Controller User Manual
Page 20
20 GuardPLC 1800 Controllers
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Communication via GuardPLC Ethernet is indicated by two small status indicators integrated
into all connecting sockets.
Additional nonsafety-related communication occurs on the field buses and is indicated by the
status indicators.
Specifications
Indicator
State
Description
Green
On
Full-duplex operation
Flashing
Collision
Off
Half-duplex operation, no collision
Yellow
On
Connection established
Flashing
Interface activity
Indicator
Connection
Description
Green
COMM 1
RS-485 interface, field bus active
COMM 2
Unassigned
COMM 3
Unassigned
Technical Specifications – GuardPLC 1800 Controllers
Attribute
1753-L28BBBM-8A, 1753-L28BBBP-8A
User memory
250 KB max user program memory
250 KB max application data memory
Watchdog time, min
10 ms
Safety time, min
20 ms
Current consumption
9 A max (with max load)
0.75 A idle current
Operating voltage
24V DC, -15…20%, w
ss
≤
15% (from a power supply with protective
separation conforming to IEC 61131-2 requirements)
Isolation voltage
50V (continuous), Basic Insulation Type, I/O to Ethernet and Ethernet to DC
power
Wiring category
(1)
Category 2 on communication ports, signal ports, and power ports
Wire size
•
I/O – 0.13…1.3 mm
2
(26…16 AWG) solid or stranded copper wire rated at
75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
•
Power – 0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper wire rated
at 75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max
•
Ethernet – RJ45 connector according to IEC 60603-7, 2 or 4-pair Category
5e minimum cable according to TIA 568-B.1, or Category 5 cable according
to ISO/IEC 24702
•
Comm: 9-pin D-sub