Specifications

(cont.)

DC (10–30V) Output Module

13

Publication 1771-IN036C-EN-P - July 2002

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Keying

Between 14 and16

Between 32 and34

Fuse

Four 4.0A, 250V normal blow fuses (1 per group); SAN-O Corporation

ST4-4.0A

FieldWiring Arm

Catalog Number 1771ĆWN

Wiring Arm Screw Torque

9 pound-inches (1.0Nm)

Certifications

(when product is marked)

UL

UL ListedIndustrial Control Equipment

CSA

CSA CertifiedProcess Control Equipment

CSA

CSA CertifiedProcess Control Equipment for Class I,

Division 2 Group A, B, C, D Hazardous Locations

CE

3

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-2, Industrial Immunity

EN 61000-6-4, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial Requirements

C-Tick

3

Australian Radiocommunications Act, compliant with:

AS/NZS 2064, Industrial Emissions

1

14 gauge wire connectedto all terminals may not allow the cover on the fieldwiring arm to close. A smaller gauge wire may

be used.

2

You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial

Automation Wiring and Grounding Guidelines.

3

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details