background image

DC (10–30V) Output Module

12

Publication 1771-IN036C-EN-P - July 2002

Outputs per module

32 (4 groups of 8)

Module Location

1771ĆA1B thru ĆA4B or later I/O Chassis

Voltage Rating

10 to 30V dc, 0.5A per output, 2A per group, 8A per module

Maximum Output Current Rating

Maximum Output Current Rating
0.5A per output (not to exceed8A per module)

2A per output group

Maximum Surge Current

2A per output for 10ms; repeatable every 2 seconds.

5A per output group for 10ms; repeatable every 2 seconds.

20A per module for 10ms; repeatable every 2 seconds.

Maximum OnĆstate Voltage Drop

1.5V dc at rated output current

Maximum OffĆstate Leakage Current

1.0mA @ 55

o

C

Output Signal Delay

On to off propagation delay 2.0msec

Off to on propagation delay 0.1msec

Power Dissipation

13.7W (max); 1.7W (min)

Thermal Dissipation

46.7 BTU/hr (max); 5.7 BTU/hr (min)

Backplane Current

330mA @ 5V dc maximum

Isolation Voltage

Testedto withstand 500V for 60s.

Conductors

Wire Size

Category

14 AWG (2.5mm

2

) to 22 AWG (0.25mm

2

) (max)

1

stranded copper

ratedat 60

o

C or greater

3/64 inch (1.2mm) insulation (max)

2

2

Environmental Conditions

Operating

Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 104°F (0

o

to 40

o

C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal

Shock)

-40 to 185°F (-40 to 185

o

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, UnpackagedShock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV indirect discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m, 3V/M Broadcast Bands, with 1kHz sine-wave 80% AM from

30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and+2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Specifications continued on next page.

Specifications