5-2 Diagnose Problems

Indication

Probable Cause

Recommended Action

Network Status

Off

Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.

Apply power to device.

Flashing Green

Device is online but has no connections in the established state.

None - device is in Idle or Program mode.

Solid Green

Device is online and has connections in the established state.

None

Flashing Red

One or more I/O connections are in timed-out state.

Check for module failure and correct as
needed.

Solid Red

Critical link failure is present with failed communication device.
Device detected error that prevents it communicating on the
network.

Verify that adapter and terminal bases are
properly installed, and reinstall, as needed.

Flashing
Red/Green

Communication faulted device - the device detected a network
access error and is in communication faulted state. Device
received and accepted an Identify Communication Faulted
Request - long protocol message.

Verify that adapter is properly installed, and
reinstall, as needed.

Indication

Probable Cause

Recommended Action

Run Status

Off

Module is commanded to stop retrieving SSI data.

Turn Run on to begin collecting SSI data.

Solid Green

Module is commanded to retrieve SSI data.

None

Up Status

Off

SSI data is not increasing, or no SSI data is being received.

None

Solid Green

SSI data is increasing.

None

Down Status

Off

SSI data is not decreasing, or no SSI data is being received.

None

Solid Green

SSI data is decreasing.

None

Comp Status

Off

Comparator function is not in use, or comparator value not
attained.

None

Solid Green

Comparator value is attained.

None

I1 Status

Off

Latching input I1 is OFF.

None

Solid Yellow

Latching input I1 is ON.

None