beautypg.com

Rockwell Automation 1794-OB8_OB8EP_OB16_OB16P_OB32P Flex I/O Digital DC Sourcing Output Modules Installation Instructions User Manual

Page 6

background image

6

Publication 1794-IN094B-EN-P - April 2004

Derating Curve for the 1794-OB16P

Specifications - 16 Output Modules 1794-OB16, -OB16P and
-OB16PK

1794-OB16

1794-OB16P, -OB16PK

Number of Outputs

16, nonisolated, sourcing

Module Location

Cat. No. 1794-TB2, -TB3, -TB3S

On-state Current

1.0mA minimum per channel
500mA maximum per channel

Output Current Rating

8.0A (16 outputs @ 0.5A)

Surge Current

2A for 50ms, repeatable every 2s

1.5A for 50ms, repeatable every 2s

Off-state Leakage

0.5mA maximum

On-state Voltage Drop

0.5V dc maximum

Isolation Voltage

Tested at 850V dc for 1s between
user and system
No isolation between individual
channels

Tested at 2121V dc for 1s between
user and system
No isolation between individual
channels

Output Signal Delay

Off to On - 0.5ms maximum
On to Off - 1.0ms maximum

Flexbus Current

80mA

60mA

Power Dissipation

5.3W maximum @ 31.2V dc

5.0W maximum @ 31.2V dc

Thermal Dissipation

Maximum 18.1 BTU/hr @ 31.2V dc

Maximum 17.0 BTU/hr @ 31.2V dc

Indicators (field side
indication, logic driven)

16 yellow status indicators

Fusing

Module outputs are not fused.
Fusing is recommended. If fusing is
desired, you must provide external
fusing. Use SAN-O MQ4-800mA
fuses

Outputs are electronically
protected.

Specifications - 24V dc 32 Output Module, Cat. No. 1794-OB32P

Number of Outputs

32 (2 groups of 16) nonisolated within groups, sourcing

Module Location

Cat. No. 1794-TB32, -TB32S

On-state Current

1.0mA minimum per channel; 500mA maximum per channel

Output Current Rating

14A maximum per module (6A total for channels 0-15; 8A total for
channels 16-31)

Surge Current

2A for 50ms, repeatable every 2s

Off-state Leakage

0.5mA maximum

On-state Voltage Drop

0.5V dc maximum

Isolation Voltage

Tested at 2121V dc for 1s between user and system
No isolation between individual channels

Output Signal Delay

Off to On - 0.5ms maximum
On to Off - 1.0ms maximum

Flexbus Current

80mA

Power Dissipation

5.3W maximum @ 31.2V dc

Thermal Dissipation

Maximum 18.1 BTU/hr @ 31.2V dc

Indicators (field side
indication, logic driven)

32 yellow status indicators

Fusing

Outputs are electronically protected.

General Specifications

On-state Voltage Range

10V dc minimum (1794-OB8EP - 19.2V dc minimum)
24V dc nominal
31.2V dc maximum

Off-state Voltage

31.2V dc maximum

Terminal Base Screw
Torque

7 pound-inches (0.8Nm)
1794-TBN - 9 pound-inches (1.0Nm)

External dc Power

‘Supply Voltage

Voltage Range

Supply Current

24V dc nominal
1794-OB8, -OB16, -OB16P, -OB32P - 10 to 31.2V dc (includes 5% ac ripple)

1794-OB8EP - 19.2 to 31.2V dc (includes 5% ac ripple)
1794-OB8 - 25mA @ 24V dc (10 to 35mA)
1794-OB8EP - 80mA @ 24V dc

1794-OB16 - 49mA @ 24V dc (20-65mA)
1794-OB16P - 60mA @ 24V dc (25 to 75mA) See derating curve.

1794-OB32P - 219mA @ 24V dc (104mA @ 10V dc;-278mA @ 31.2V dc)

Dimensions (with
module installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

Keyswitch Position

2

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage
Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF
Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

1

12AWG (4mm

2

) stranded copper wire rated at 75°C or higher

3/64 inch (1.2mm) insulation maximum
2

Certifications (when
product is marked)

2

UL

UL Listed Industrial Control Equipment (all)

C

UL

US

UL Listed Industrial Control Equipment, certified for US and

Canada (1794-OB32P)

C

UL

US

UL Listed for Class I, Division 2, Groups A, B, C and D

Hazardous locations , certified for US and Canada (1794-OB8)

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations (1794-OB8, -OB8EP, -OB16, -OB16P)

EEx

2

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,
Protection “n”(Zone 2) - (1794-OB8, -OB8EP, -OB16, -OB16P)

CE

2

European Union 89/336/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity (all)

C-Tick

2

- Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions (all)

1

You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of

Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

0

15

10

25

20

30

31.2

10 20 30 40 50 55 60

Ambient Temperature oC

The area within the curve represents the safe operating range for the module

under various conditions of user supplied 24V dc supply voltages and ambient temperatures.

= Normal mounting safe operating range, (includes ).

= Other mounting positions (including inverted horizontal) safe operating range

37

32

28.5

27.5

Normal Mounting – Horizontal

Other Mounting (including Vertical, and Inverted Horizontal Mounting)

in

V

On-State

Voltage

(V dc)