Publication 1794-IN094B-EN-P - April 2004

Installation Instructions

FLEX I/O Digital dc Output Modules

1794-OB8, -OB8EP, -OB8EPK, -OB16, -OB16P,
-OB16PK, -OB32P

(Modules with a K in the last position of the catalog number are
conformally coated to meet noxious gas requirements of
ISA/ANSI-71.040-1985 Class G3 Environment.)

European Hazardous Location Approval

The following output modules are European Zone 2
approved: 1794-OB8, -OB8EP, -OB8EPK, -OB16,
-OB16P and -OB16PK.

Important User Information

Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.ab.com/manuals/gi) describes some
important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential
damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information,
circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc. is prohibited.

Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause
an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and
understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions
help you:

identify a hazard

avoid a hazard

recognize the consequence

WARNING

When you insert or remove the module while backplane power is

on, an electrical arc can occur. This could cause an explosion in

hazardous location installations. Be sure that power is removed or

the area is nonhazardous before proceeding.

ATTENTION

FLEX I/O is grounded through the DIN rail to chassis ground. Use

zinc plated yellow-chromate steel DIN rail to assure proper grounding.

The use of other DIN rail materials (e.g. aluminum, plastic, etc.) that

can corrode, oxidize, or are poor conductors, can result in improper or

intermittent grounding.

ATTENTION

Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2

industrial environment, in overvoltage Category II applications (as

defined in IEC publication 60664-1), at altitudes up to 2000 meters

without derating.
This equipment is considered Group 1, Class A industrial

equipment according to IEC/CISPR Publication 11. Without

appropriate precautions, there may be potential difficulties

ensuring electromagnetic compatibility in other environments due

to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be

mounted within an enclosure that is suitably designed for those

specific environmental conditions that will be present and

appropriately designed to prevent personal injury resulting from

accessibility to live parts. The interior of the enclosure must be

accessible only by the use of a tool. Subsequent sections of this

publication may contain additional information regarding specific

enclosure type ratings that are required to comply with certain

product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529,

as applicable, for explanations of the degrees of protection

provided by different types of enclosure. Also, see the appropriate

sections in this publication, as well as the Allen-Bradley publication

1770-4.1 ("Industrial Automation Wiring and Grounding

Guidelines"), for additional installation requirements pertaining to

this equipment.

ATTENTION

Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause

internal damage and affect normal operation. Follow these guidelines

when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

If available, use a static-safe workstation.

European Zone 2 Certification
This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this
equipment has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3
equipment intended for use in potentially explosive atmospheres, given in
Annex II to this Directive. The examination and test results are recorded in
confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been
assured by compliance with EN 50021.