4. Connect individual output wiring (OUT16 to

OUT31) to numbered terminals on the 16-33 row

(B) as indicated in the table below.

5. Connect the associated power to the +V2 terminal

(43, 45, 47 or 49) on the 34-51 row (C) as indicated

in the table below.

6. Connect the associated output common (-V2)for

OUT16 to OUT31 to COM2 (terminals 44, 46, 48

or 50) on the 34 to 51 row (C).

7. If continuing power to the next terminal base,

connect a jumper from terminal 35, 37, 39 or 41

(+V1) and 43, 45, 37 or 49 (+V2) on this base unit

to the power terminal on the next base unit.

8. If continuing output common return to the next

base unit, connect a jumper from terminal 36, 38,

40 or 42 (COM1) and 44, 46, 48 or 50 (COM2) on

this base unit to common on the next base unit

(refer to the installation instructions for the next

type of terminal base unit).

Note: Total current draw through the terminal base is
limited to 10A. Separate power connections may be
necessary.

Wiring Connections for the 1794-OB32P (used with
1794-TB32 or -TB32S Terminal Base Unit)

1794-TB32 and -TB32S Terminal Base Wiring for 1794-OB32P

Configuring Your 1794-OB8EP and -OB8EPK Output Module

You configure your output module by setting bits in the
configuration word (see below).

Output

Output Terminal

Common

Power

Output 0

A-0

Connect common
to terminals 36,
38, 40 and 42

Connect power
to terminals 35,
37, 39 and 41

Output 1

A-1

Output 2

A-2

Output 3

A-3

Output 4

A-4

Output 5

A-5

Output 6

A-6

Output 7

A-7

Output 8

A-8

Output 9

A-9

Output 10

A-10

Output 11

A-11

Output 12

A-12

Output 13

A-13

Output 14

A-14

Output 15

A-15

Output 16

B-17

Connect common
to terminals 44,
46, 48 and 50

Connect power
to terminals 43,
45, 47 and 49

Output 17

B-18

Output 18

B-19

Output 19

B-20

Output 20

B-21

Output 21

B-22

Output 22

B-23

Output 23

B-24

Output 24

B-25

Output 25

B-26

Output 26

B-27

Output 27

B-28

Output 28

B-29

Output 29

B-30

Output 30

B-31

Output 31

B-32

For Outputs 0 thru 15, use +V1 and COM1

+V1 dc power

Power terminals 35, 37, 39 and 41

Com1 dc Return

Common terminals 36, 38, 40 and 42

For Outputs 16 thru 31, use +V2 and COM2

+V2 dc power

Power terminals 43, 45, 47 and 49

Com2 dc Return

Common terminals 44, 46, 48 and 50

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

F7

F6

F5

F4

F3

F2

F1

F0

Reserved (see note)

Write

Not used

FR

O
7

O
6

O
5

O
4

O
3

O
2

O
1

O
0

Write

Where: O = Output - O0 corresponds to output 0, O1 corresponds to output 1, etc.

F = Overload fault bits - 1 = fault present; 0 = no fault

FR = Fault reset bit - 1 = reset output; 0 = no change

Note: The unused lower byte in read word 1 floats during operation. Do not use this byte for fault status.
See Programming below.

Output

Output Terminal

Common

Power

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

NC

+V2 = Terminals 43, 45, 47 and 49

Outputs

Outputs

+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2

NC

+V1 = Terminals 35, 37, 39 and 41

COM1 = Terminals 36, 38, 40 and 42

NC = No connections (terminals 16, 33, 34 and 51)

COM2 = Terminals 44, 46, 48 and 50

NC

NC

(1794-TB32 shown)

A

B

C