Connecting Wiring for the 1794-OB8, -OB8EP, -OB8EPK, -OB16,
-OB16P and -OB16PK

1. Connect individual output wiring to numbered

terminals on the 0-15 row (A) as indicated in the

table below (1794-OB8 - Terminals 0-7;

1794-OB16 and -OB16P(K) - terminals 0-15;

1794-OB8EP(K) - even numbered terminals 0-14).

2. Connect the associated -V output common to the

corresponding terminal on the 16-33 row (B) for

each output as indicated in the table below.

(Commons are internally connected together.)

1794-OB8EP(K) - connect associated output common to
odd-numbered terminals on row A or associated terminals on row B.

3. Connect +V dc power to terminal 34 on the 34-51

row (C).

4. Connect -V dc common to terminal 16 on the

16-33 row (B).

5. If daisychaining power to the next terminal base,

connect a jumper from terminal 51 (+V dc) on this

base unit to terminal 34 on the next base unit.

6. If continuing -V dc common to the next base unit,

connect a jumper from terminal 33 (common) on

this base unit to terminal 16 on the next base unit.

Wiring Connections for the 1794-OB8, -OB16, -OB16P and
-OB16PK using the 1794-TB2, -TB3, or -TB3S

Wiring Connections for the 1794-OB8EP and -OB8EPK

1794-TB2, -TB3 and -TB3S Terminal Base Wiring for 1794-OB8,
-OB8EP, -OB8EPK, -OB16, -OB16P and -OB16PK

1794-TBN Terminal Base Wiring for the 1794-OB8EP

Connecting Wiring for the 1794-OB32P

1. Connect individual output wiring (OUT0 to

OUT15) to numbered terminals on the 0-15 row

(A) as indicated in the table below.

2. Connect the associated power to the +V1 terminal

(35, 37, 39 or 41) on the 34-51 row (C) as indicated

in the table below.

3. Connect the associated output common (-V1)for

OUT0 to OUT15 to COM1 (terminal 36, 38, 40 or

42) on the 34 to 51 row (C).

Output

1

Output Terminal

Common Terminal

Output 0

A-0

B-17

Output 1

A-1

B-18

Output 2

A-2

B-19

Output 3

A-3

B-20

Output 4

A-4

B-21

Output 5

A-5

B-22

Output 6

A-6

B-23

Output 7

A-7

B-24

Output 8

A-8

B-25

Output 9

A-9

B-26

Output 10

A-10

B-27

Output 11

A-11

B-28

Output 12

A-12

B-29

Output 13

A-13

B-30

Output 14

A-14

B-31

Output 15

A-15

B-32

+V dc

C-34 thru C-51 (C-34 and C-51 for 1794-TB2)

Common

B-16 thru B-33

1

1794-OB8 - Outputs 0 thru 7; 1794-OB16, -OB16PK and -OB16P- Outputs 0

thru 15

1794-TB2, -TB3, TB3S

1794-TBN

Output

Output
Terminal

Common
Terminal

1

Output
Terminal

Common
Terminal

2

Output 0

A-0

A-1/B-17

B-0

C-1

Output 1

A-2

A-3/B-18

B-2

C-3

Output 2

A-4

A-5/B-19

B-4

C-5

Output 3

A-6

A-7/B-20

B-6

C-7

Output 4

A-8

A-9/B-21

B-8

C-9

Output 5

A-10

A-11/B-22

B-10

C-11

Output 6

A-12

A-13/B-23

B-12

C-13

Output 7

A-14

A-15/B-24

B-14

C-15

+V dc

C-34 thru C-51 (C-34 and C-51 for 1794-TB2, -TBN)

Common

B-16 thru B-33 (B-16 and B-33 for 1794-TBN)

1

1794-TB2, -TB3, -TB3S - A-1, A-3, A-5, A-7, A-9, A-11, A-13 and A-15 are connected

together inside the module to 24V dc common.

2

1794-TBN - C-1, C-3, C-5, C-7, C-9, C-11, C-13 and C-15 are connected together inside the

module to 24V dc common.

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Outputs

Commons

(1794-TB3 shown)

Connect -V (Supply Common) to terminal B-16
Connect +V (Supply +Voltage) to terminal C-34

-V

Voltage
In +V

Voltage
Out +V

Voltage

Terminals 35 thru 50 not available on 1794-TB2

A

B

C

Common

-V

Common

(Use B-33 and C-51 for daisy-chaining to next terminal base unit.)

Total current draw through the terminal base is limited to 10A. Separate power
connections to each terminal base may be necessary.

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

+V

COM

+V

COM

B

C

Even Numbered I/O Terminals 0 thru 14

Odd Numbered I/O Terminals 1 thru 15

Connect -V (Supply Common) to terminal B-16
Connect +V (Supply +Voltage) to terminal C-34

(Use B-33 and C-51 for daisy-chaining to next terminal base unit.)

Total current draw through the terminal base is limited to 10A. Separate power
connections to each terminal base may be necessary.