4 - troubleshoot the processor system, Use the plc 5 processor status indicators, Troubleshoot the processor system – Rockwell Automation 1785-LTx,D178510.3 QUICK START CLASSIC PLC-5 PROG User Manual
Page 16: Chapter, Use the plcć5 processor status indicators
Chapter
4
Publication 1785Ć10.3 - October 1996
Troubleshoot the Processor
System
Use the PLCĆ5 Processor
Status Indicators
(page 4-1)
1
BATT
PROC
FORCE
COMM
Indicator
Color
Description
Probable Cause
Recommended Action
PROC
green
(steady)
processor in RUN mode and
fully operational
normal operation
no action required
green
(blinking)
Processor memory being
transferred to EEPROM
normal operation
no action required
red
(blinking)
major fault
runĆtime error
Check major fault bit in status file (S:11)
for error definition. Clear fault bit, correct
problem, and return to RUN mode.
red
(steady)
major fault
•
user RAM has
checksum error
•
memory module
error
•
Clear memory and reload program.
•
Check backplane switch settings
and/or insert correct memory module.
off
processor in program load or
TEST mode or is not receiving
power
Check power supply and connections.
PROC
REM I/O
all red
(steady)
internal
diagnostics have
failed
Power down, reseat processor and
power up. Then, clear memory and
reload your program. Replace EEPROM
with new program. Then, if necessary,
replace the processor.
FORCE
amber
(steady)
forces enabled
normal operation
no action required
amber
(blinking)
forces present, but not
enabled
normal operation
no action required
off
no forces present
normal operation
no action required
BATT
red
(steady)
battery low
Replace battery within 1Ć2 days (typical).
off
battery is good
normal operation
no action required
ADPT
(continues)
green
(steady)
processor is in adapter mode
normal operation
no action required
COMM
BATT
REM I/O
ADPT
PROC
FORCE
FAULT
ACTIVE
RUN
REM
R
U
N
P
R
O
G
Use the PLCĆ5 Processor
Status Indicators