10 High Current 8 Input/8 Output ArmorBlock I/O Module Series B
Publication 1792D-IN005D-EN-P - February 2002
Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate. Consumption occurs when data
changes and the master produces new input data to the I/O block.
Refer to the table below for the word/bit definitions.
Refer to the table below for byte/bit descriptions.
The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.
Bit
07
06
05
04
03
02
01
00
Produces 0
OL7
OL6
0L5
0L4
0L3
0L2
0L1
0L0
Produces 1
NL7
NL6
NL5
NL4
NL3
NL2
NL1
NL0
Produces 2
I7
I6
I5
I4
I3
I2
I1
I0
Consumes 0
O7
O6
O5
O4
O3
O2
O1
O0
Where: OL=Output Overload NL=Output No Load I=Input O = Output
Byte
Bit
Description
Produces 0
00-07
Output overload status
Produces 1
00-07
Output no load status
Produces 2
00-07
Input point status
Consumes 0
00-07
Output bits: When the bit is set (1), the output will
be turned on. Bit 00=output 00, bit 01=output 01,
bit 02=output 02, bit 03=output 03, bit 04=output
04, bit 05=output 05, bit 06=output 06, bit
07=output 07.