ArmorPOINT™ 24V DC Analog Output Modules 9

Publication 1738-IN004B-EN-E - July 2011

Interpret Status Indicators

Indicator Status for Modules

Status

Description

Module status

Off

No power applied to device.

Green

Device operating normally.

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Flashing red

Recoverable fault.

Red

Unrecoverable fault – may require device replacement.

Flashing red/green Device is in self-test.

Network status Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing red

One or more I/O connections is in timed-out state.

Red

Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.

Flashing red/green Communication faulted device – the device has detected a

network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request – long protocol message.

MOD

NET

0

1

1738-OE2CM12/A

Analog Current Out

0

1

1738-OE2CM12

45755

Module status indicator
Network status indicator

I/O status indicators