Interpret status indicators, Indicator status for modules – Rockwell Automation 1738-OE2VM12 ArmorPoint 24V dc Analog Output Modules, Series A User Manual
Page 9
![background image](/manuals/579569/9/background.png)
ArmorPOINT™ 24V DC Analog Output Modules 9
Publication 1738-IN004B-EN-E - July 2011
Interpret Status Indicators
Indicator Status for Modules
Status
Description
Module status
Off
No power applied to device.
Green
Device operating normally.
Flashing green
Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Flashing red
Recoverable fault.
Red
Unrecoverable fault – may require device replacement.
Flashing red/green Device is in self-test.
Network status Off
Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Flashing green
Device is online but has no connections in the established state.
Green
Device is online and has connections in the established state.
Flashing red
One or more I/O connections is in timed-out state.
Red
Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.
Flashing red/green Communication faulted device – the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request – long protocol message.
MOD
NET
0
1
1738-OE2CM12/A
Analog Current Out
0
1
1738-OE2CM12
45755
Module status indicator
Network status indicator
I/O status indicators