Rockwell Automation 1738-OE2VM12 ArmorPoint 24V dc Analog Output Modules, Series A User Manual
Page 13

ArmorPOINT™ 24V DC Analog Output Modules 13
Publication 1738-IN004B-EN-E - July 2011
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5…95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM @ 80 MHz…2000 MHz
10V/m with 200 Hz 50% pulse 100% AM @ 900 Mhz
10V/m with 200 Hz 50% pulse 100% AM @ 1890 Mhz
EFT/B immunity
IEC 61000-4-4:
±3 kV @ 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80% AM @ 150 kHz…80 MHz
Emissions
CSPR 11:
Group 1, Class A
Enclosure type rating
Meets IP65/66/67 (when marked)