Interpreting the dot matrix displays, Interpreting the dot matrix displays -3 – Rockwell Automation 1747-KFC15 SLC500 CONTROLNET RS-232 USER MANUAL User Manual
Page 35

Troubleshooting the KFC15 Module
5-3
1747-5.34 - June 1998
Interpreting the Dot Matrix Displays
Under normal conditions, the dot matrix display should be displaying the
ControlNet network address as well as the ControlNet network status.
During operation, the dot matrix display is used to indicate hardware fault
conditions. When the STATUS LED is solid or flashing red, the display
shows a number indicating the type of hardware fault. The following table
gives a description of the faults.
Channel A or
B (viewed
separately)
OFF
Channel disabled or
unused
Program network for redundant
media if required.
SOLID GREEN
Channel good—data is
being received and
transmitted on this
channel
None
FLASHING
GREEN - OFF
Temporary errors or
device is not on-line
None. Unit will correct itself.
FLASHING RED -
GREEN
Bad network
configuration
Check network setup then cycle
power to the KFC15 module.
FLASHING RED -
OFF
Media fault or no other
nodes present on the
network
Check media for broken cables,
loose connector, missing
terminators, etc.
STATUS
OFF
No power is applied to
the KFC15 module
None
SOLID GREEN
Normal operation—the
module is OK
None
FLASHING
GREEN
The KFC15 is not
properly configured
Check and change parameter
settings.
SOLID RED
Critical fault—the
KFC15 has detected an
unrecoverable fault and
must be replaced
Contact your authorized Allen-
Bradley representative or
distributor.
FLASHING RED
Non-critical fault—the
KFC15 has detected a
recoverable fault
Reconfigure or reset the KFC15.
LED
State
Probable Cause
Recommended Action