Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual
Page 21

1734 POINT I/O Dual Port EtherNet/IP Adapter 21
Publication 1734-IN041B-EN-P - October 2013
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, surrounding air, max
55 °C (131 °F)
Temperature, nonoperating
IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports
Conducted RF immunity
IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz