Specifications – Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual
Page 18
18 1734 POINT I/O Dual Port EtherNet/IP Adapter
Publication 1734-IN041B-EN-P - October 2013
Specifications
POINT I/O EtherNet/IP Adapter — 1734-AENTR, Series B
Attribute
Value
Expansion I/O capacity, max
• 63 modules
• 5 rack optimized connections (for digital modules only)
• 31 direct connections
(1)
• 1734-AENTR backplane current output = 0.8 A.
• Actual number of modules can vary.
• Add up current requirements of modules you want to use to
make sure they do not exceed the amperage limit of 0.8 A for
the 1734-AENTR adapter.
• Backplane current can be extended beyond 0.8 A by
1734-EP24DC or 1734-EPAC backplane extension power
supplies.
• Add multiple 1734-EP24DC or 1734-EPAC modules to reach
the 63 module max.
(1)
Maximum 31 direct connections for standard I/O or maximum 20 direct connections if any safety I/O module resides in
the backplane.
POINTBus current requirements, max
• 50 mA (Catalog number 1734-IB4D)
• 75 mA (Catalog numbers 1734-IB2, 1734-IB4, 1734-IB8,
1734-IV2, 1734-IV4, 1734-OB2, 1734-OB4, 1734-OB8,
1734-OB2E, 1734-OB2EP, 1734-OB4E, 1734-OB8E, 1734-OV2E,
1734-OV4E, 1734-232ASC, 1734-485ASC, 1734-ARM,
1734-IV8, 1734-OV8E, 1734-IE4C, 1734-IE8C, 1734-OE4C,
1734-IA4, 1734-IM4, 1734-OA4, 1734-IR2E, 1734-IE2C,
1734-OE2C, 1734-IE2V, 1734-OE2V, 1734-IA2, 1734-IM2,
1734-OA2)
• 80 mA (Catalog number 1734-OW2, 1734-OW4)
• 100mA (Catalog numbers 1734-OX2, 1734-8CFG)
• 110mA (Catalog number 1734-SSI)
• 160mA (Catalog numbers 1734-IJ2, 1734-IK2)
• 175mA (Catalog number 1734-IT2I)
• 180mA (Catalog numbers 1734-VHSC5, 1734-VHSC24)
• 220 mA (Catalog number 1734-IR2, 1734-IR2E)
Module location
Starter module - left side of the 1734 system
Power Supply
Attribute
Value
Input voltage rating
24V DC @ 10A
Input voltage, range
10...28.8V DC
Field side power, max
24V DC @ 400 mA
Inrush current, max
6 A for 10 ms