1734 POINT I/O Dual Port EtherNet/IP Adapter 17
Publication 1734-IN041B-EN-P - October 2013
Network
status
Off
Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing green
Device is on-line but has no CIP connections in the
established state.
Solid green
Device on-line and has CIP connections in the established state.
Flashing red
One or more CIP connections in timed-out state. Check for I/O module
failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing red/green Module self-test
Network
Activity
Off
No link established with Port 1 or Port 2.
Flashing green
Transmit or receive activity present on Port 1 and/or Port 2 @ 100 Mb.
Transmit or receive activity present on Port 1 and/or Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
Solid green
Link established with Port 1 and/or Port 2 @ 100 Mb.
Link established with Port 1 and Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
Solid yellow
Link established with Port 1 and/or Port 2 @ 10 Mb.
Flashing yellow
Transmit or receive activity present on Port 1 and/or Port 2 @ 10 Mb.
Link 1 or
Link 2
Activity /
Status
Off
No link established.
Solid green
Link established @ 100 Mbps.
Flashing green
Transmit or receive activity present on indicated port @ 100 Mbps.
Solid yellow
Link established @ 10 Mbps.
Flashing yellow
Transmit or receive activity present on indicated port @ 10 Mbps.
POINTBus
status
Off
Device is not online.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Flashing green
Device is online but has no connections in the established state.
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established.
Flashing red
Recoverable fault occurred:
• At cycle power, the number of expected modules does not equal the
number of modules present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred - the adapter is bus off.
Flashing red/green LED powerup test is in progress.
System
power
Off
Not active. Adapter power is off or there is a DC-DC converter problem.
Solid green
System power is on. DC-DC converter output is active (5V).
Field power Off
Not active. Adapter power is off.
Solid green
Power is on. 24V input is present.
Indicator Status for Modules