1734 POINT I/O Dual Port EtherNet/IP Adapter 17

Publication 1734-IN041B-EN-P - October 2013

Network

status

Off

Device is not on-line

- Device has not completed dup_MAC_id test.

- Device not powered - check module status indicator

Flashing green

Device is on-line but has no CIP connections in the
established state.

Solid green

Device on-line and has CIP connections in the established state.

Flashing red

One or more CIP connections in timed-out state. Check for I/O module
failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Flashing red/green Module self-test

Network
Activity

Off

No link established with Port 1 or Port 2.

Flashing green

Transmit or receive activity present on Port 1 and/or Port 2 @ 100 Mb.
Transmit or receive activity present on Port 1 and/or Port 2.

One port @ 100 Mb and the other port @ 10 Mb.

Solid green

Link established with Port 1 and/or Port 2 @ 100 Mb.
Link established with Port 1 and Port 2.

One port @ 100 Mb and the other port @ 10 Mb.

Solid yellow

Link established with Port 1 and/or Port 2 @ 10 Mb.

Flashing yellow

Transmit or receive activity present on Port 1 and/or Port 2 @ 10 Mb.

Link 1 or

Link 2
Activity /

Status

Off

No link established.

Solid green

Link established @ 100 Mbps.

Flashing green

Transmit or receive activity present on indicated port @ 100 Mbps.

Solid yellow

Link established @ 10 Mbps.

Flashing yellow

Transmit or receive activity present on indicated port @ 10 Mbps.

POINTBus

status

Off

Device is not online.

Device has not completed Dup_MAC_ID test.

Device not powered - check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established.

Flashing red

Recoverable fault occurred:

• At cycle power, the number of expected modules does not equal the

number of modules present.

• A module is missing.

• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred - the adapter is bus off.

Flashing red/green LED powerup test is in progress.

System
power

Off

Not active. Adapter power is off or there is a DC-DC converter problem.

Solid green

System power is on. DC-DC converter output is active (5V).

Field power Off

Not active. Adapter power is off.

Solid green

Power is on. 24V input is present.