Configure Your Module
To configure your module in RSLogix 5000, complete the following.
1. Configure your adapter.
Refer to the user manual for your adapter for information on
how to configure the adapter and add modules to the I/O
configuration to include selecting a controller and
communication module.
2. Add a 1734-IJ or 1734-IK specialty module, according to the
instructions in your adapter user manual.
3. From the Connection dialog, perform the following.
a. Select a value for the Requested Packet Interval (RPI) entry.
• Default value is 80.0 milliseconds.
• Range is 2.0 to 750.0 milliseconds.
b. Leave the following unchecked.
• Inhibit Module
• Major Fault On Controller If Connection Fails
While in Run Mode
4. Complete entries for the following dialogs, as explained in this
chapter.
• Fault/Program Action
• Counter Configuration
Use the Help Button
From the Fault/Program Action and Counter Configuration dialogs,
click Help at the bottom of the dialog for information about how to
complete entries on the dialogs.
From a warning dialog, click Help at the bottom fo the dialog to get
information about that specific error.