Configuration data – Rockwell Automation 1734-IK Encoder/Counter Modules User Manual User Manual
Page 36
![background image](/manuals/579502/36/background.png)
Publication 1734-UM006B-EN-P - August 2005
3-4 Input and Output Data
Zero frequency Detected (ZD) - This bit is operational when
frequency configurations are programmed (configurations: period/rate
[5], rate measurement [7]).
In period/rate [5] configuration, counts are acquired during
the ON state of the Z input. At very low frequencies the counter
saturates, indicating a zero frequency detect. The time it takes to
determine a zero frequency in these two configurations can be
as long as 6.7 seconds ( 16,777,216 counts x 1/5MHz x 2 half
cycles of Z ).
In rate measurement [7] configuration pulses on the A input
are counted over a sample interval specified by the time base.
The time it takes to determine a zero frequency in this
configuration will be determined by the sample interval, for
example, time base = 0.300 second (300 milliseconds) to
determine ZF.
Configuration Data
The following represents the configuration data used by the module.
Parameter
Configuration Information
Size (bytes)
1
Set/Get
Counter Configuration
1
2
Set/Get
Filter Selection
1
3
Set/Get
Decimal Position
1
4
Set/Get
Reserved
1
5
Set/Get
Time Base
2
6
Set/Get
Gate Interval
1
7
Set/Get
Scalar
1
8
Set/Get
Rollover Value
4
9
Set/Get
Preset Value
4
10
Set/Get
Counter Control SS Value
1