beautypg.com

Rockwell Automation 1734-ADN, ADNX Point I/O DeviceNet Adapter Installation Instructions User Manual

Page 26

background image

26 POINT I/O DeviceNet Adapter

Publication

1734-IN026A-EN-P - April 2005

Dimensions Inches

(Millimeters)

3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)

Operational Temperature

IEC60068-2-1 (Test Ad, Operating Cold)
IEC60068-2-2 (Test Bd, Operating Dry Heat)
IEC60068-2-14 (Test Nb, Operating Thermal Shock)

-20...55

o

C (-4...131

o

F)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged Non-operating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock)

-40...85

o

C (-40...185

o

F)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged Non-operating Damp
Heat)
5...95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating)
5g @ 10-500Hz

Shock Operating
Shock Non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g
IEC 60068-2-27(Test Ea, Unpackaged Shock) 50g

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC6100-4-2
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200HZ 50% Pulse 100%Am at 900MHz

EFT/B Immunity

IEC 61000-4-4
+4kV at 5kHz on power ports
+2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5
+1kV line-line (DM) and +2kV line-earth (CM) on power ports
+2kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC61000-4-6
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80 MHz

Enclosure Type Rating

None (open-style)