16 POINT I/O DeviceNet Adapter

Publication

1734-IN026A-EN-P - April 2005

Indicator

Indication

Probable Cause

Take This Action

System
Power

Off

• Not active
• Field power is OFF.
• DC-DC converter

problem

• Check adapter

configuration.

• Turn field power

ON.

• Contact

Customer
Support.

Green

• System power is ON.
• DC-DC converter is

active (5V).

None

Field Power

Off

• Not active
• Field power is OFF.

• Check adapter

configuration.

• Turn field power

ON.

Green

Power is ON with 24V present.

None

43933

System power

Field power

Adapter status

Network status
Subnet status

Status indicators for 1734-ADNX adapters

Adapter
Status

Field
Power

DeviceNet
Status

1734-ADNX

Subnet
Status

System
Power