Communications Interface Specifications (continued)

Expansion I/O Capacity

Up to 13 modules (13 times 75mA = 0.975, just under the
limit of 1.0A), based on POINTBus current requirements
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure
they do not exceed the amperage limit of the adapter. Total
expansion is up to 63 modules - 13 modules maximum with
the adapter. Add 1734-EP24DC modules for an additional
17 modules (or less based on current requirements), up to
63 modules maximum.

Cat. No.

PointBus Current Requirements

1734-IB2

75mA

1734-IB4

75mA

1734-IB8

75mA

1734-IV2

75mA

1734-IV4

75mA

1734-OB2

75mA

1734-OB4

75mA

1734-OB8

75mA

1734-OB2E

75mA

1734-OB2EP

75mA

1734-OB4E

75mA

1734-OB8E

75mA

1734-OV2E

75mA

1734-OV4E

75mA

1734-OW2

80mA

1734-OX2

100mA

1734-IE2C

75mA

1734-OE2C

75mA

1734-IE2V

75mA

1734-OE2V

75mA

1734-IA2

75mA

1734-IM2

75mA

1734-OA2

75mA

1734-IJ2

160mA

1734-IK2

160mA

1734-IR2

220mA

1734-IT2I

175mA

1734-SSI

110mA

1734-VHSC5

180mA

1734-VHSC24

180mA

1734-232ASC

75mA