Writing to the memory module – Rockwell Automation 1785-M100_ME16_ME32_ME64 INSTL DATA ENHANCED ETHERNET PLC-5 User Manual
Page 6
![background image](/manuals/579474/6/background.png)
19632
Locking
Bar
Ejector
Tab
PLCĆ5
processor
Card Guides
Installation Data
PLCĆ5/11, Ć5/20, Ć5/30, Ć5/40, Ć5/40L, Ć5/60
Programmable Controller Memory Module
Installation Data
Enhanced PLCĆ5 and Ethernet PLCĆ5
Programmable Controller Memory Module
6
Use the following steps to store a program on your memory module.
Important: If you are using a 1785-L40B series A, revision B or a
1785-L60B series A, revision B processor, you must have the Global
Status Flag file set to zero. Access this file through the channel
configuration screen for channels configured for DH+ communications. If
the Global Status Flag file is set to any number except zero and you try to
write to a memory module, you will lose processor memory and a
processor fault occurs.
1.
Insert the memory module into the processor using the installation
procedure in this document (see page 5).
2.
On the I/O chassis backplane, set backplane switch 6 to the ON
position and switch 7 to the OFF position (see page 4).
3.
Install the processor into the I/O chassis.
4.
Turn on power to the processor and I/O chassis.
5.
Put the processor in Program or Rem Program mode.
If you try to write to a memory module when the processor is in any
other mode, you receive a
NO ACCESS OR PRIVILEGE
VIOLATION
message.
6.
Develop or download your program online (make sure you initialize
your data table values).
Writing to the Memory
Module
18593