18 POINT I/O EtherNet/IP Adapter

Publication

1734-IN590B-EN-P - February 2005

Environmental
Conditions

Operational
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55

° C (-4 to 131° F)

Storage
Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock): -40 to 85

° C (-40 to 185° F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5
to 95% noncondensing

Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

Operating

30g peak acceleration

Nonoperating

50g peak acceleration

Vibration

IEC 60068-2-6 (Test Fc, Operating)
Tested 5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF
Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% pulse 100%AM from 900MHz

EFT/B Immunity

IEC 61000-4-4:
+4kV at 5.0kHz on power ports
+2kV at 5.0kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on communications
ports
+1kV line-line(DM) and +2kV line-earth(CM) on power ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions

CISPR 11
Group 1, Class A

Enclosure Type Rating

None (open-style)