Rockwell Automation 1771-ODD INSTL.DATA AC/DC (220/44)INPUT User Manual
Installation instructions, 1771-odd series b), Contents prevent electrostatic damage
Publication 1771Ć5.20 - January 1999
AC (120V) Isolated Output
Module, 16 Outputs
(1771-ODD Series B)
Use this document as a guide when installing the catalog number
1771-ODD series B output module.
To
See page
Prevent Electrostatic Discharge
1
Understand Compliance to European Union Directives 2
Important Preinstallation Considerations
2
Calculate Power Requirements
4
Setting the Mode of the FuseĆBlown Jumper
4
Key the Backplane Connector
5
Install the Module andFieldWiring Arm
6
Connect Wiring to the FieldWiring Arm
7
For this reference information
See page
Interpret the Status Indicators
9
Replacing a Fuse
10
CSA Hazardous Location
11
Specifications
12
The ac isolated output module is shipped in static-shielded packaging
to guard against electrostatic discharge damage. Observe the
following precautions when handling the module.
Electrostatic Discharge Damage
!
ATTENTION: Electrostatic discharge can damage
integrated circuits or semiconductors if you touch
backplane connector pins. Follow these guidelines
when you handle the module:
•
Touch a grounded object to discharge static potential
•
Wear an approved wrist-strap grounding device
•
Do not touch the backplane connector or
connector pins
•
Do not touch circuit components inside the module
•
If available, use a static-safe work station
•
When not in use, keep the module in its original
static-shielded packaging
Installation Instructions
Contents
Prevent Electrostatic
Damage