beautypg.com

Rockwell Automation 1771-OA AC (120V) Output Module User Manual

Page 9

background image

AC Output Module

9

Publication 1771-IN080A-EN-P - November 2002

Figure 2

Using an Output Module to drive an Input Module

L1

2.5K ohm

10 Watt

Resistor

A
O
1
2
3
4

5
6
7
B

L1

A
O
1
2
3
4

5
6
7
B

L2

L2

Typically

ac Low

ac High

AC (120V) Output Module

1771-IA

AC (120V) Input Module

1771-OA

L1

2.5K ohm

10 Watt

Resistor

A
O
1
2
3
4

5
6
7
B

L1

L2

Typically

ac High

AC (120V) Output Module

1771-OA

AC/DC (120V) Input Module

1771-IAD

L2

ac Low

11885-I

!

ATTENTION

The 1771–OA module outputs are not isolated.
Maintain isolation between phases in multiple
phase systems.