Connect wiring to the module – Rockwell Automation 1771-OA AC (120V) Output Module User Manual
Page 7
AC Output Module
7
Publication 1771-IN080A-EN-P - November 2002
The 1771–OA module is a modular component of the 1771 I/O
system requiring a properly installed system chassis. Refer to
publication 1771–IN075 for detailed information on acceptable
chassis, proper installation and grounding requirements. Limit the
maximum adjacent slot power dissipation to 15W maximum.
You make connections to the module through the 1771-WA field
wiring arm shipped with the module. The arm pivots on the chassis
to connect with the 8 terminals on the front of the module. The
wiring arm allows the module to be removed from the chassis
without disconnecting wiring.
1. Make certain all power is removed from the module before
making wiring connections.
2. Swing the wiring arm up into position on the front of the module.
The locking tab on the module will secure it into place.
3. Make your connections to the field wiring arm as shown in
Figure 1. (Use the label on the front of the wiring arm to identify
your wiring.)
IMPORTANT
The field wiring arm terminal identification
number is not the same as the number of the bit
which controls that output.
You should identify the labels on the wiring arm with the name or
number of the device connected at each terminal.
Connect Wiring to the
Module