Rockwell Automation 1738-ACNR ArmorPoint ControlNet Adapter, Series A User Manual
Page 12

Publication 1738-IN016B-EN-E - March 2005
12 ArmorPoint ControlNet Adapter, Series A
General Specifications (continued)
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity
IEC 61000-4-4:
±4kV at 5kHz on power ports
±3kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±2kV line-earth(CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions
CSPR 11:
Group 1, Class A
Enclosure Type Rating
Meets IP65/66/67 (when marked)
Mounting Base Screw Torque
#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
Wiring Category
1
1 - on power ports
1 - on communications ports
Weight
Imperial (Metric)
0.80 lb. (0.36 kg)
Certifications:
2
(when product is marked)
c-UL-us UL Listed Industrial Control Equipment,
certified for US and Canada
CE
European Union 89/336/EEC EMC
Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
CI
ControlNet Int’l conformance tested to ControlNet
specifications
1.
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial Automation
Wiring and Grounding Guidelines".
2.
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.