Module Configuration Word
Word 4 of the configuration data file contains the Enable/Disable Cyclic Calibration bit as
shown in the table below.
Specifications
To Select
Make these bit settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Cyclic
Calibration
Enabled
(1)
(1)
When enabled, an autocalibration cycle is performed on all enabled channels every 5 minutes.
0
Disabled
1
General Specifications
Specification
Value
Dimensions, (H x W x D)
90 x 40 x 87 mm (height including mounting tabs is 110 mm)
3.54 x 1.58 x 3.43 in. (height including mounting tabs is 4.33 in.)
Approximate Shipping Weight
(with carton)
220 g (0.53 lbs.)
Temperature, nonoperating
-40…85 °C (-40…185°F)
Temperature, operating
0…55 °C (-32…131 °F)
Humidity, operating
5…95% non-condensing
Altitude, operating
2000 m (6561 ft)
Vibration, operating
10…500 Hz, 5 g, 0.030 in. max. peak-to-peak
Shock, operating
30 g
Vendor ID code
1
Product type code
10
Product code
64
Hazardous environment class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI 12.12.01
(C-UL under CSA C22.2 No. 213)
Noise immunity
NEMA standard ICS 2-230
Radiated and conducted emissions
EN50081-2 Class A
ESD immunity (EN61000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated immunity (EN61000-4-3)
10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier
Fast transient burst (EN61000-4-4)
2 kV, 5 kHz
Surge immunity (EN61000-4-5)
1 kV galvanic gun
Conducted immunity (EN61000-4-6)
10V, 0.15 …80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is