MicroLogix 1762-OW8 Relay Output Module
13
Publication 1762-IN003B-EN-P - June 2013
Power supply distance rating
6
Isolated groups
Group 1: Outputs 0…3
Group 2: Outputs 4…7
Output group to backplane isolation
Verified by one of the following dielectric tests: 1836V AC for 1 sec. or
2596V DC for 1 sec.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec. or
2596V DC for 1 sec.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor ID code
1
Product type code
7
Product code
120
Relay Contact Ratings
Volts (max.)
Continuous
Amps per Point
(max.)
Amperes
(1)
(1)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
Voltamperes
Make
Break
Make
Break
240V AC
2.5 A
7.5 A
0.75 A
1800 VA
180 VA
120V AC
15 A
1.5 A
125V DC
1.0 A
0.22 A
(2)
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58 A. For DC voltage applications less than 48V, the make/break rating
for relay contacts cannot exceed 2A.
28 VA
24V DC
2.0 A
1.2 A
28 VA
Output Specifications
Specification
Value