Rockwell Automation 1762-OW8 MICROLOGIX RELAY OUTPUT MODULE User Manual
Page 12
12
MicroLogix 1762-OW8 Relay Output Module
Publication 1762-IN003B-EN-P - June 2013
Certifications
Certification (when product is
marked)
(1)
(1)
See product certification link at
Certificates, and other certification details.
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S and Canada.
See UL File E334470.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Autralian Rediocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC
Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Output Specifications
Specification
Value
Voltage category
AC/DC normally open relay
Operating voltage range
5…265V AC
5…125V DC
Number of outputs
8
Bus current draw (max.)
80 mA @ 5V DC (0.40W)
90 mA @ 24V DC (2.16W)
Heat dissipation (max.)
2.9 Total Watts
Signal delay (max.) – resistive load
On Delay: 10 ms
Off Delay: 10 ms
Off-state leakage (max.)
0 mA
On-state current (min.)
10 mA @ 5V DC
Continuous current per point (max.)
2.5 A (
See “Relay Contact Ratings” on page 13.
)
Continuous current per common
(max.)
8 A
Continuous current per module (max.) 16 A