Specifications – Rockwell Automation 1762-OW8 MICROLOGIX RELAY OUTPUT MODULE User Manual
Page 11

MicroLogix 1762-OW8 Relay Output Module
11
Publication 1762-IN003B-EN-P - June 2013
Specifications
General Specifications
Specification
Value
Dimensions, H x W x D
90 x 40 x 87 mm
height including mounting tabs is 110 mm
3.543 x 1.5753 x 3.425 in.
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
228 g (0.50 lbs.)
Temperature, nonoperating
-40…85 °C (-40…185 °F)
Temperature, operating
0…55 °C (-32…131 °F)
Operating humidity
5…95% non-condensing
Operating altitude
2000 m (6561 ft)
Vibration
Refer to the MicroLogix 1200 Controllers Installation Instructions,
pu
Shock, operating
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI 12.12.01
(C-UL under CSA C22.2 No. 213)
Noise Immunity
NEMA standard ICS 2-230
Radiated and Conducted Emissions
EN50081-2 Class A
ESD Immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is 30…1000
MHz.