beautypg.com

Table 10 environmental specifications – Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module User Manual

Page 19

background image

SLC 500 8-Point Analog Output Module 19

Publication 1746-IN026A-EN-P - July 2003

SLC 500 is a trademark of Rockwell Automation.
Belden is a trademark of Belden Inc.

Table 10 Environmental Specifications

Specification

1746-NO8I

1746-NO8V

Operating Temperature

0°C to +60°C (+32°F to +140°F)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Humidity

5 to 95% non-condensing

Vibration

Operating: 5.0G at 10 to 500Hz, One Octave/min sweep, 10 sweeps

Shock

Operating: 30G (3 pulses, 11 ms)
Non-Operating: 50G (3 pulses, 11 ms)

Free Fall (drop test)

Portable, 2.268 kg (5 lbs) or less at 0.762 m (30 in.) (six drops)
Portable, 2.268 kg (5 lbs) or more at 0.1016 m (4 in.) (three flat drops)

Noise Immunity

NEMA standard ICS 2-230

Agency Certification

UL/C-UL:
UL Listed Industrial Control Equipment
UL Listed Industrial Control Equipment for use in Canada
UL Listed Industrial Control Equipment for use in Class I, Division 2
Hazardous Locations Groups A, B, C, D

CE marked for all applicable directives

C-Tick marked for all applicable acts

This manual is related to the following products: