Table 9 configuration and status specifications – Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module User Manual

Page 18

background image

18 SLC 500 8-Point Analog Output Module

Publication 1746-IN026A-EN-P - July 2003

Table 9 Configuration and Status Specifications

Specification

1746-NO8I

1746-NO8V

Module ID Code

Class 1: 3527
Class 3: 12727

Class 1: 3528
Class 3: 12728

Number of Output Channels

8

8

Current Output Ranges

(selectable for each channel)

4 to 20 mA

0 to 20 mA

0 to 21 mA

0 to 21.5 mA

n/a

Voltage Output Ranges

(selectable for each channel)

n/a

-10 to +10V dc

-10.25 to +10.25V dc

0 to 10V dc

0 to 5V dc

1 to 5V dc

SLC Data Formats

(selectable for each channel)

Scaled engineering units

Scaled for PID

Proportional counts

1746-NO4 format

User-defined scale

Optional Output Data Parameters

User defined scale limits

Output clamping limit

Output alarm limits

Ramp rate/limit

Preset fault value

Output behavior under fault condition (reset, hold, preset)

Alarms latch

Reset latched alarms

Error Reporting

24V power failure

Open current loop

Module/SLC resetting

Fatal channel error