beautypg.com

Specifications – Rockwell Automation 1769-OF4CI CompactLogix 1769-OF4CI Module User Manual

Page 22

background image

22 Compact 1769-OF4CI Isolated Analog Output Module

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

Specifications

Specification

1769-OF4CI

Dimensions

118 mm (height) x 87 mm (depth) x 35 mm
(width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in
(width)
height including mounting tabs is 5.43 in.

Approximate Shipping Weight
(with carton)

270g (0.6 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in.
peak-to-peak

Shock

Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)

Agency Certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location,
Groups A, B, C, D (ISA 12.12-01, C-UL under
CSA C22.2 No. 213)

Radiated and Conducted Emissions

IEC 61000-6-4 and CISPR 11 Group 1, class A

Electrical /EMC:

The module has passed testing at the
following levels:

ESD Immunity (IEC 61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC 61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude

modulation

Fast Transient Burst (IEC 61000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC 61000-4-5)

1 kV galvanic gun

Conducted Immunity (IEC 61000-4-6)

10V dc, 0.15 to 80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 1000 MHz.