Specifications – Rockwell Automation 1769-OF4CI CompactLogix 1769-OF4CI Module User Manual
Page 22
22 Compact 1769-OF4CI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Specifications
Specification
1769-OF4CI
Dimensions
118 mm (height) x 87 mm (depth) x 35 mm
(width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in
(width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
270g (0.6 lbs.)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Operating Temperature
0°C to +60°C (32°F to +140°F)
Operating Humidity
5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in.
peak-to-peak
Shock
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Agency Certification
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location,
Groups A, B, C, D (ISA 12.12-01, C-UL under
CSA C22.2 No. 213)
Radiated and Conducted Emissions
IEC 61000-6-4 and CISPR 11 Group 1, class A
Electrical /EMC:
The module has passed testing at the
following levels:
• ESD Immunity (IEC 61000-4-2)
• 4 kV contact, 8 kV air, 4 kV indirect
• Radiated Immunity (IEC 61000-4-3)
• 10 V/m, 80 to 1000 MHz, 80% amplitude
modulation
• Fast Transient Burst (IEC 61000-4-4)
• 2 kV, 5 kHz
• Surge Immunity (IEC 61000-4-5)
• 1 kV galvanic gun
• Conducted Immunity (IEC 61000-4-6)
• 10V dc, 0.15 to 80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 1000 MHz.