20 Compact 1769-OF4CI Isolated Analog Output Module

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

Channel Configuration Words

The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 16 and 17 correspond to
channel 3.

E = Channel Enable: (0 = Disabled, 1 = output Enabled, process
changes)

Reserved = Set to zero

SIU = System interrupt low clamp, under-range alarms: (0 = Disabled,
1 = Enabled)

SIO = System interrupt high clamp, over-range alarms: (0 = Disabled,
1 = Enabled)

LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled,
1 = Enabled)

ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)

FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)

PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)

HI = Hold for initialization: (0 = Disabled, 1 = Enabled)

PFE = Program/idle to fault enable: (0 = Disabled, 1 = Enabled)

Word/Bit 15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word 0

E

Reserved

SIU SIO LA

ER

FM

PM

HI

PFE

Word 1

Reserved

Output Data

Format Select

Reserved

Output
Type/Range