120V ac FLEX I/O 8 Input Module (Cat. No. 1794ĆIA8)

Publication 1794Ć5.9

Increasing the Input Delay Time

You can increase the input delay time (DT) for channels 00 through 07. Select the
input delay time by setting the corresponding bits in the output image table
(complementary word) for the module.

For example, to increase the off-to-on delay time to 12ms for an ac input module at
address rack 1, module group 0, set bits 02, 01, and 00 as shown below.

0 1 1

11 10

17 16 15 14 13 12

DT = 00-07

Fill File

Source

Destination

Length

3

#O:010

1

FLL

Write DT to complement

of input module.

O:010

00

I:000

Write Delay Time on system startup.

= 3 Octal or 3 Decimal

09 08 07 06 05 04 03 02 01 00

15 14 13 12 11 10

Dec.

(Octal)

07 06 05 04 03 02 01 00

Delay Times

Bits

Description

Maximum Delay Time

02

01

00

Delay Time for Inputs 00-07

Off to On

On to Off

0

0

0

Delay Time 0 (default)

8.6ms

26.6ms

0

0

1

Delay Time 1

9ms

27ms

0

1

0

Delay Time 2

10ms

28ms

0

1

1

Delay Time 3

12ms

30ms

1

0

0

Delay Time 4

17ms

35ms

1

0

1

Delay Time 5

26ms

44ms

1

1

0

Delay Time 6

43ms

61ms

1

1

1

Delay Time 7

78ms

96ms