Rockwell Automation 1753-IB8XOB8 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module Installation Instructions User Manual
Page 19

GuardPLC 8-Digital Inputs and 8-Digital Outputs Module 19
Publication 1753-IN010A-EN-P - October 2005
No. of Outputs (L-)
2 (not electrically isolated), reference pole S+
Output Voltage
≥L+ minus 2V
Output Current (L+)
Output Current (L-)
Channels 1 to 3 and 5 to 7: 0.5 A @ 60°C (140°F)
Channels 4 and 8: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)
Channels 4- and 8-: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)
Max. lamp load:
L+ channel 1-3, 5-7
L+ channel 4 and 8
L- channel 4- and 8-
10 W
25 W
25 W
Max. inductive load:
L+ channel 1-3, 5-7
L+ channel 4 and 8
L- channel 4- and 8-
500 mH
500 mH
500 mH
Minimum Load
2 mA per channel
Internal Voltage Drop
max. 2.0V dc @ 2 A
Off-State Leakage Current
max. 1 mA @
2V
Overload Response
Shut down of the concerned output with cyclic reconnection
Total Output Current
max. 7 A with exceeding shut down of all outputs with cyclic reconnection
Pulsed Outputs
No. of Outputs
2 (not electrically isolated)
Output Voltage
≥L+ minus 4V
Output Current (L+)
Approx. 60 mA
Minimum Load
none
Switching Time
≤ 100 micro-seconds
Overload Response
2 x
≥ 19.2V, short-circuit current 60 mA @ 24V
Environmental Conditions
Storage Temperature :
-40...+85 °C (-40...+185 °F)
• IEC 60068-2-1 (Test Ab, Unpackaged non-operating cold)
• IEC 60068-2-2 (Test Bb, Unpackaged non-operating dry heat)
• IEC 60068-2-14 (Test Na, Unpackaged non-operating thermal shock)
Operating Temperature:
0...+60 °C (+32...140 °F)
• IEC 60068-2-1 (Test Ad, operating cold)
• IEC 60068-2-2 (Test Bd, operating dry heat)
• IEC 60068-2-14 (Test Nb, operating thermal shock)
Vibration
1 g @ 10…150 Hz
• IEC 60068-2-6 (Test Fc, operating)
Shock, Operating
15 g
• IEC 60068-2-27 (Test Ea, unpackaged shock)
Relative Humidity
10 to 95% non-condensing
• IEC 60068-2-30 (Test Db, unpackaged non-operating damp heat)
Emissions
Group 1, Class A
ESD Immunity
6 kV contact discharges
8 kV air discharges