Troubleshoot with LED Indicators
Indicator
State
Condition
24V dc
On
24V dc operating voltage present.
Off
No operating voltage.
RUN
On
This is the normal status of the module.
A routine, which has been loaded into the module, is executed.
The module processes input and output signals, carries out communication, and
performs hardware and software tests.
Flashing
The module is in STOP mode and is not executing a routine.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.
Off
The module is in ERROR_STOP (see ERROR).
ERROR
On
• A hardware error has been detected by the module. The module goes to
ERROR_STOP and the execution of the routine is halted. Hardware errors are
errors in the module, errors in one or more of the digital input and output
modules, or errors in the counters.
• A software error in the operating system has been detected by the module.
• The watchdog has reported an error due to exceeded cycle time.
All system outputs are reset and the module ceases all hardware and software tests.
The module can only be restarted by a command from the programming software.
Off
No errors are detected.
PROGress
On
The upload of a new module configuration is in progress.
Flashing
The upload of a new operating system into the Flash ROM is in progress.
Off
No upload of module configuration or operating system in progress.
FORCE
On
The module is executing a routine (RUN) and FORCE mode is activated by the user.
Flashing
The module is in STOP, but Forcing has been initiated and will be activated when the
module is started.
Off
Forcing is OFF.
FAULT
On
• The routine (logic) has caused an error.
• The module configuration is faulty.
• The upload of a new operating system was not successful and the operating
system is corrupted.
Flashing
An error has occurred during a Flash ROM write cycle.
One or more I/O errors have occurred.
Off
None of the above errors has occurred.
OSL
Flashing
Emergency Operating System Loader is active.
BL
Flashing
Boot Loader unable to load operating system or unable to start COMM operating
system loader.
Module status can be interrogated through the programming software. For more information, refer to the
GuardPLC System User Manual, publication number 1753-UM001.