Chapter 1 Produce and Consume a Tag
The table provides a description of error messages for situations where an RPI is
not accepted.
Scenario Description
Software Version
I/O Fault Message
RPI of consumed tag is not within the range of the
producer. Producer does not support RPI negotiation or is
not configured to provide a default RPI to the consumer.
Any
(Code 0111) Requested Packet Interval (RPI) out of range.
RPI of consumed tag is not within the range of the
producer. Producer is returning default RPI. Consumer
does not support negotiation or is not configured to
accept RPI from producer.
18 and later
(Code 0112) Requested Packet Interval (RPI) out of range.
17 and earlier
(Code 0112) Unknown Error.
RPI of consumer is out of range, but producer provides a
default RPI and consumer can accept default RPI. Network
path contains bridge that does not support extended error
information.
18 and later
(Code 0112) Requested Packet Interval (RPI) out of range.
Producer provided RPI blocked by the network path.
RPI of consumer is out of range, but producer provides a
default RPI and consumer can accept RPI provided by
producer. Network path contains scheduled NUT.
18 and later
(Code 0112) Requested Packet Interval (RPI) out of range.
Cannot use producer provided RPI over a path containing
a scheduled network.