Scenario 3 – Rockwell Automation Logix5000 Controllers Produced and Consumed Tags Programming Manual User Manual
Page 27

Produce and Consume a Tag Chapter 1
Scenario 3
The RPI is outside the range of the producing controller’s RPI Limits. A default
RPI is set up for the producing controller. But, the network path contains a bridge
that blocks the negotiated RPI to prevent an interruption to other controllers on
the network.
Version 17 and earlier: The RPI requested by the consumed tag is not within the
range of the producer. The connection is rejected and a 0112 error is reported that
the connection failed. You must re-enter an RPI that is within the range
configured on the produced tag. If a version 17 consumer is trying to connect with
a version 18 producer and the RPI is outside the range of the producer, a 0112
error reports the connection failed.
Tip:
See
for an explanation of the error messages.
Version 18 and later: The RPI requested by the consumed tag is not within the
RPI limitation range of the producer. The producer is configured to provide an
RPI default. The producer sends the default RPI to the consumer, but the
consumer controller is not set up to accept a default RPI from the producer. The
negotiated RPI is disabled to prevent an interruption to the multicast connection.
A 0112 error message is reported and you must re-enter an RPI within the range of
the producer’s limits.
Rockwell Automation Publication 1756-PM011F-EN-P - October 2014
27