General Specifications (continued)

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30g

Non-Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900MHz|

10V/m with 200Hz 50% Pulse 100%AM at 1890MHz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on power ports

±2kV at 5kHz on signal ports

±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2 line-earth(CM) on power ports

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±2kV line-earth(CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Conductors

Publication DN-6.7.2

Enclosure

Meets IP67

Supply Voltages/Voltage Ranges

DNet Power: 11V dc to 25V dc;

Auxiliary Power: 10V dc to 30V dc

Supply Power/Current Ratings

DNet current:1.6A;

Input current: 50mA;

Output power: 60VA DC-13/SQ;

Outputs 4A total;

Auxiliary current:4A

Isolation voltage (continuous-voltage
withstand rating)

Tested to withstand 750V dc for 60 seconds

Wire Size

Use 14-22 AWG wire with insulation temperature rating of
75°C min.See Publication DN-6.7.2; Category: 2.

Wiring Category

1

2 - on signal ports

2 - on power ports

2 - on communications ports

8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE