General Specifications (continued)
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
Non-Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900MHz|
10V/m with 200Hz 50% Pulse 100%AM at 1890MHz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on power ports
±2kV at 5kHz on signal ports
±2kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2 line-earth(CM) on power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
±2kV line-earth(CM) on communications ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Conductors
Publication DN-6.7.2
Enclosure
Meets IP67
Supply Voltages/Voltage Ranges
DNet Power: 11V dc to 25V dc;
Auxiliary Power: 10V dc to 30V dc
Supply Power/Current Ratings
DNet current:1.6A;
Input current: 50mA;
Output power: 60VA DC-13/SQ;
Outputs 4A total;
Auxiliary current:4A
Isolation voltage (continuous-voltage
withstand rating)
Tested to withstand 750V dc for 60 seconds
Wire Size
Use 14-22 AWG wire with insulation temperature rating of
75°C min.See Publication DN-6.7.2; Category: 2.
Wiring Category
1
2 - on signal ports
2 - on power ports
2 - on communications ports
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE