beautypg.com

Specifications – Rockwell Automation 1792D-8BT8PE ArmorBlock MaXum 8 In/8 Out Module with Ground Lug User Manual

Page 15

background image

ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 15

Publication

1792D-IN055A-EN-P - October 2004

The following table describes individual I/O status indicators.

Specifications

I/O Status Indicators

Function

Module Status Indicator

Point
Indicator

1

Status

Outputs

Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red

None
Yellow
Orange
Red
Orange
Red

Output not energized
Output energized
Output shorted - auto restart
Output shorted - latching
Output no load - auto restart
Output no load - latching

Inputs

Green
Green
Module Status blink red
Module Status blink red

None
Yellow
Red
Blink red

No valid input
Valid input
Short on input connector

1

Off wire on input connector

1

Only the first LED of each input connector will light as red when twin inputs are used.

8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE

Input Specifications

Maximum

Minimum

Inputs per block 8 - 3 wire or dry contact PNP devices or 4 - 4 wire PNP devices

Sensor Source Current (per connector)

100mA total

-

Off-wire Sense Current

0.5mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Output Specifications

Maximum

Minimum

Outputs per block 8 sourcing outputs labeled O0 through O7

Off Peak Blocking Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.5A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

4.0A

-

Surge Current - for 10ms, repeatable
every 2s

2.4A

-

No Load Sense Current (On-state)

0.18A

-